BRGZQ - HALON 1301

Product Identification

Product ID:HALON 1301
MSDS Date:09/01/1990
FSC:1680
NIIN:01-072-7463
MSDS Number: BRGZQ

Responsible Party
GREAT LAKES CHEMICAL CORP
HIGHWAY 52 NW
WEST LAFAYETTE, IN 47906
US

Emergency Phone: 501-862-5141

Info Phone: 317-497-6100

Preparer: RESEARCH SERVICES DEPT.

Cage: 2E394

Contractor
PACIFIC SCIENTIFIC CO HTL/KIN-TECH DIVISION
DUARTE, CA 91010 US

Telephone: 818-359-9317/602-796-1100

Cage: 05167

Ingredients

TRIFLUOROBROMOMETHANE (HALON 1301) (SARA III)

CAS: 75-63-8

RTECS: PA5425000

OSHA PEL 1000 PPM

ACGIH TLV: 1000 PPM; 9293

Hazards

Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:HALON 1301 HAS ANESTHETIC AND CARDIAC
EFFECTS ABOVE 10% BY VOLUME. BELOW 10% IT IS CONSIDERED SAFE FOR
0-5 MINUTE EXPOSURES. SMOKING IN THE PERESENCE OF HALON MAY CAUSE
FORMATION OF TOXIC AND/OR IRRIT ATING DECOMPOSITION PRODUCTS WHICH
ARE INHALED WITH THE SMOKE.
Explanation of Carcinogenicity:THIS PRODUCT IS NOT LISTED BY NTP, IARC,
OR OSHA
Effects of Overexposure:ANESTHETIC EFFECTS ARE SIMILAT TO MILD
INTOXICATION. OVEREXPOSURE MAY LEAD TO ASPHYXIATION
(UNCONSCIOUSNESS & DEATH).
Medical Cond Aggravated by Exposure:CARDIAC CONDITIONS MAY BE
AGGRAVATED BY OVEREXPOSURE.

First Aid

First Aid:INHAL:REMOVE PERSON TO FRESH AIR; IF NOT BREATHING, GIVE
ARTIFIVIAL RESPIRATION. IF BREATHING IS DIFFICULT, GIVE OXYGEN. GET
MEDICAL ATTENTION. SKIN:FLUSH W/WATER. GET MEDICAL ATTENTION IF
FROSTBITE O CCURS. EYES:FLUSH W/WATER FOR AT LEAST 15 MINS. GET
MEDICAL ATTENTION. NOTE:EPINEPHRINE IS CONTRAINDICATED IN TREATMENT
OF OVEREXPOSURE TO PRODUCT.

Fire Fighting

Flash Point:NON-FLAMMBLE
Extinguishing Media:PRODUCT IS A FIRE EXTINGUISHING AGENT. USE MEDIA
SUITABLE FOR FLAMMABLE MATERIALS IN THE AREA.
Fire Fighting Procedures:WEAR SELF-CONTAINED BREATHING APPARATUS. USE
WATER SPRAY TOCOOL CYLINDERS INVOLVED IN FIRE.
Unusual Fire/Explosion Hazard:ABOVE 1000F PRODUCT MAY RELEASE HF, HBR,
CARBONYL FLUORIDE, AND/OR CARBONLY BROMIDE. THESE GASES ARE
IRRITATING AND POTENTIALLY TOXIC.

Accidental Release

Spill Release Procedures:EVACUATE AREA. WEAR SELF-CONTAINED BREATHING
APPARATUS. VENTILATE ENCLOSED AREAS IN CASE OF DISCHARGE.
Neutralizing Agent:NO INFORMATION GIVEN ON MSDS BY MFR.

Handling

Handling and Storage Precautions:PROTECT CYLINDER FROM PHYSICAL DAMAGE.
STORE BELOW 125F. SECURE CYLINDERS DURING STORAGE.
Other Precautions:NONE

Exposure Controls

Respiratory Protection:WEAR NIOSH APPROVED SELF-CONTAINED BREATHING
APPARATUS AT CONCENTRATIONS >10,000 PPM AS RECOMMENDED BY NIOSH.
CONSULT ANSI & OSHA FOR REGULATIONS ON RESPIRTOR USEAGE. AVOID
PROLONGED EXPOSURE TO EXCES SIVE CONCENTRATIONS.
Ventilation:INDOOR AREAS SHOULD BE WELL VENTILATED. USE LOCAL EXHAUST
WHERE MATERIAL IS HANDLED AND/OR TRANSFERRED.
Protective Gloves:LINED NEOPRENE OR LEATHER
Eye Protection:CHEMICAL SAFETY GOGGLES; NO CONTACTS
Other Protective Equipment:NO INFORMATION GIVEN ON MSDS BY MFR.
Work Hygienic Practices:DETERMINE THAT PIPING IS EMPTY BEFORE DOING
MAINTENANCE WORK. PERIODICALLY CHECK CYLINDERS TO ENSURE VALVES ARE
NOT LEAK
Supplemental Safety and Health
KEY2:KT THIS ITEM IS A FIRE EXTINGUISHER BOTTLE FOR AIRCRAFT. IT IS
PRESSURIZED BY NITROGEN. THE CONTRACTOR SUPPLIED 2 MSDS'S, 1 FOR
NITROGEN & 1 FOR THE HALON: SEE P/N IND A, THIS NSN.

Chemical Properties

HCC:N1
NRC/State Lic Num:NONE
Boiling Pt:B.P. Text:-72F,-58C
Melt/Freeze Pt:M.P/F.P Text:-270F,-168C
Vapor Pres:6200 MM
Vapor Density:5.1
Spec Gravity:1.57
Evaporation Rate & Reference:NOT AVAILABLE
Solubility in Water:0.03% BY WEIGHT
Appearance and Odor:ODORLESS, COLORLESS GAS

Stability

Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES & MATL CONTAINING OWN O2. HALON
WON'T EXTINGUISH FIRES OF THESE MATERIALS.
Stability Condition to Avoid:NO INFORMATION GIVEN ON MSDS BY MFR.
Hazardous Decomposition Products:HYDROGEN FLUORIDE, HYDROGEN BROMIDE,
BROMINE, CARBONYL FLUORIDE & CARBONYL BROMIDE.
Conditions to Avoid Polymerization:WILL NOT OCCUR

Disposal

Waste Disposal Methods:RETURN CYLINDERS TO GREAT LAKES CHEMICAL
CORPORATION, EL DORADO, ARKANSAS. HMIS:DISPOSE I/A/W FEDERAL,
STATE & LOCAL REGULATIONS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.